Column and slab repair by FRP strengthening

​Partial column volume reinforcement ratio is insufficient, and fiber reinfroced polymer(FRP)strengthening is used. The two and three layer hollow slab, carbon fiber fabric is strengthened.

slab repair by FRP strengthening

column strengthening by anchoring adhesive

Project overview

The office complex was built in 1994, with a total construction area of 4038.30m2, 6 main building frames, 2 floors of auxiliary buildings, and a total height of 23.7m. The project is renovated and renovated by using the original structure form, retaining the supporting components such as columns and beams of the original building, and changing the original use function. The 1-3 level is transformed into a cultural and educational exhibition base for disaster prevention and mitigation. The 4-6 layer is transformed into office space and staff dormitories, and the staircase is renovated.


The design scheme for reconstruction and reinforcement is determined

The main structure of the main building of the office building is basically good, but the concrete strength grade is generally lower than the design requirement (C30), especially the three or four layer, and the concrete strength grade is only C15. The main rib diameter of the five or six story column is 18mm, which is less than 20 mm of the design. The mortar strength of the auxiliary building wall is significantly lower than the current design and specification requirements.


  • The axial compression ratio of some columns exceeds the limit and the reinforcement is strengthened by increasing section.

  • Partial column volume reinforcement ratio is insufficient, and FRP strengthening is used.

  • The two and three layer hollow slab, carbon fiber fabric is strengthened.

  • The mortar strength of the auxiliary building wall is insufficient, and reinforcement mesh and cement mortar are used to reinforce it.

  • The bulk density of the light block is less than 8KN/m3 in the partition wall.


Retrofitting MethodRetrofitting MethodRetrofitting Materials




Component


Cloumn

Enlargement section

Steel bar and high strength grouting material

FRP strengtheningCarbon fiber fabric 300g
BeamEnlargement section

Reinforced concrete C30

SlabFRP strengtheningCarbon fiber fabric 200g

Masonry

Reinforcing steel mesh mortar reinforcemen

Steel mesh, M10 cement mortar

Steel rebar(B-HRB335、C-HRB400)、Q235B steel plate 、200g carbon fiber fabirc(Ⅱ grade)、300g carbon fiber fabirc(Ⅱ grade)、steel plate bonding adhesive(A grade)、anchoring adhesive(A grade)、wire rod welding wire(EX50XX ).